Technical Specifications
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 122
Subfeed 1
Subfeed Phase Overcurrent 14501 — 1 — Active on Alarm
Subfeed Phase Overcurrent 14502 — 1 — Active on Warning
Subfeed Neutral Overcurrent 14503 — 1 — Active on Alarm
Subfeed Ground Overcurrent 14504 — 1 — Active on Alarm
Subfeed 2
Subfeed Phase Overcurrent 14515 — 1 — Active on Alarm
Subfeed Phase Overcurrent 14516 — 1 — Active on Warning
Subfeed Neutral Overcurrent 14517 — 1 — Active on Alarm
Subfeed Ground Overcurrent 14518 — 1 — Active on Alarm
Subfeed 64
Subfeed Phase Overcurrent 15383 — 1 — Active on Alarm
Subfeed Phase Overcurrent 15384 — 1 — Active on Warning
Subfeed Neutral Overcurrent 15385 — 1 — Active on Alarm
Subfeed Ground Overcurrent 15386 — 1 — Active on Alarm
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 37 Liebert EXC
™
, Liebert FDC
™
, Liebert FPC
™
, Liebert PPC
™
, Liebert RDC
™
, Liebert RX
™
, Liebert
STS2/PDU
™
- Status and Coil (continued)
Controller Liebert LDMF
Liebert Products
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC,
Liebert RX, Liebert STS2/PDU
Available Points
Data Label
Status Coil
Number
of Bits Scale Notes / Units