Technical Specifications

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 122
Subfeed 1
Subfeed Phase Overcurrent 14501 1 Active on Alarm
Subfeed Phase Overcurrent 14502 1 Active on Warning
Subfeed Neutral Overcurrent 14503 1 Active on Alarm
Subfeed Ground Overcurrent 14504 1 Active on Alarm
Subfeed 2
Subfeed Phase Overcurrent 14515 1 Active on Alarm
Subfeed Phase Overcurrent 14516 1 Active on Warning
Subfeed Neutral Overcurrent 14517 1 Active on Alarm
Subfeed Ground Overcurrent 14518 1 Active on Alarm
Subfeed 64
Subfeed Phase Overcurrent 15383 1 Active on Alarm
Subfeed Phase Overcurrent 15384 1 Active on Warning
Subfeed Neutral Overcurrent 15385 1 Active on Alarm
Subfeed Ground Overcurrent 15386 1 Active on Alarm
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 37 Liebert EXC
, Liebert FDC
, Liebert FPC
, Liebert PPC
, Liebert RDC
, Liebert RX
, Liebert
STS2/PDU
- Status and Coil (continued)
Controller Liebert LDMF
Liebert Products
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC,
Liebert RX, Liebert STS2/PDU
Available Points
Data Label
Status Coil
Number
of Bits Scale Notes / Units