Technical Specifications
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 120
Table 37 Liebert EXC
™
, Liebert FDC
™
, Liebert FPC
™
, Liebert PPC
™
, Liebert RDC
™
, Liebert RX
™
, Liebert
STS2/PDU
™
- Status and Coil
Controller Liebert LDMF
Liebert Products
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC,
Liebert RX, Liebert STS2/PDU
Available Points
Data Label
Status Coil
Number
of Bits Scale Notes / Units
Panel 1 – Panelboard Main 1 (if panelboards are installed)
Panel Summary Alarm 10065 — 1 — Active on Alarm
Panel Overvoltage 10066 — 1 — Active on Alarm
Panel Undervoltage 10067 — 1 — Active on Alarm
Panel Phase Overcurrent 10068 — 1 — Active on Alarm
Panel Phase Overcurrent 10069 — 1 — Active on Warning
Panel Neutral Overcurrent 10070 — 1 — Active on Alarm
Panel Ground Overcurrent 10071 — 1 — Active on Alarm
Panel 2 – Panelboard Main 2 (if panelboards are installed)
Panel Summary Alarm 10082 — 1 — Active on Alarm
Panel Overvoltage 10083 — 1 — Active on Alarm
Panel Undervoltage 10084 — 1 — Active on Alarm
Panel Phase Overcurrent 10085 — 1 — Active on Alarm
Panel Phase Overcurrent 10086 — 1 — Active on Warning
Panel Neutral Overcurrent 10087 — 1 — Active on Alarm
Panel Ground Overcurrent 10088 — 1 — Active on Alarm
Panel 4 – Panelboard Main 4 (if panelboards are installed)
Panel Summary Alarm 10116 — 1 — Active on Alarm
Panel Overvoltage 10117 — 1 — Active on Alarm
Panel Undervoltage 10118 — 1 — Active on Alarm
Panel Phase Overcurrent 10119 — 1 — Active on Alarm
Panel Phase Overcurrent 10120 — 1 — Active on Warning
Panel Neutral Overcurrent 10121 — 1 — Active on Alarm
Panel Ground Overcurrent 10122 — 1 — Active on Alarm
Panel 1 Position 1
Branch Overcurrent 10133 — 1 — Active on Alarm
Branch Overcurrent 10134 — 1 — Active on Warning
Branch Undercurrent Warning 10135 — 1 — Active on Alarm
Panel 1 Position 2
Branch Overcurrent 10146 — 1 — Active on Alarm
Branch Overcurrent 10147 — 1 — Active on Warning
Branch Undercurrent Warning 10148 — 1 — Active on Alarm
Panel 1 Position 84
Branch Overcurrent 11212 — 1 — Active on Alarm
Branch Overcurrent 11213 — 1 — Active on Warning
Branch Undercurrent Warning 11214 — 1 — Active on Alarm