User's Manual

Pin Configuration
4
3.0 PIN CONFIGURATION
Table 1 Relay contact card pin configuration
Terminal
Block
Pin
DB25
Pin Function Operation
1 1 UPS Fault Closed if no UPS failure*
—2 Not Used
—3 Not Used
4 4 UPS Fault Closed if UPS fails*
5 5 Summary Alarm**
Closed if SUMMARY ALARM**
occurs*
6 6 Summary Alarm**
Closed if no alarm conditions
are present*
77
Signal Ground (for UPS
Any Mode Shutdown)
—8 Not Used
9 9 Common - Low Battery
10 10 Low Battery Closed if battery is OK
11 11 Low Battery
Closed if LOW BATTERY
point occurs.
12 Not Used
13 Not Used
14 14
UPS Any Mode
Shutdown (short to pin 7)
Turn UPS output OFF
when connected to pin 7*
15 15 On UPS Closed if ON UPS (inverter) power*
16 16 On Battery
Closed if ON BATTERY power
(Utility failure)
17 17
Common - UPS Fault,
Summary Alarm, On UPS,
On Battery, On Bypass
18 18 On Battery
Closed if not ON Battery power
(Utility OK)
19 Not Used
20 Not Used
21 Not Used
22 Not Used
23 Not Used
24 24 On Bypass Closed if ON BYPASS*
25 Not Used
* Feature not available on PSI products
** A Summary Alarm occurs when any of the following conditions exists:
Utility power is out of the acceptable range (voltage and/or frequency).
UPS is in BYPASS MODE (load not on Inverter power).
UPS battery is LOW (<2 minutes of battery power remaining).
UPS fault has occurred.