User's Manual

Installation
2
2.0 INSTALLATION
Parts and Tools Required
• Intellislot Interface for Relay Contacts card and required
cable assembly
• #2 (medium) Phillips or small flat-head screwdriver
Instructions
1. Turning off the UPS prior to installation
is suggested, although not required.
2. Locate the Intellislot port on the UPS.
The Intellislot port is on the rear of some
units (GXT, Nfinity and PowerSure PSI);
on the Liebert NX, the port is inside the
front door. Refer to your UPS user man-
ual for port location and orientation.
3. Remove the two retaining screws from
the Intellislot port cover plate on the
UPS.
NOTE: Save the screws for re-assembly (described in
Step 5).
4. The card and slot are keyed to insert in one position only.
Initially, the card should slide in freely as you carefully
align screw holes. As you feel it click into place, press
firmly to ensure solid seating in the slot.
5. Using the screwdriver, secure the card to the UPS chassis
with the two retaining screws. Make sure the screws are
snug, not tight, to avoid damage to the device.
INTELLISLOT
PORT ON A UPS
Remove
screws
CARD AND SLOT ORIENTATION
CorrectIncorrect