MONITORING INTELLISLOT™ USER MANUAL Interface Card for Relay Contacts
CONTENTS 1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . 1 2.0 INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . 2 3.0 PIN CONFIGURATION . . . . . . . . . . . . . . . . . . . . 4 4.0 JUMPER SETUP . . . . . . . . . . . . . . . . . . . . . . . 5 5.0 CONTACTING TECHNICAL SUPPORT . . . . . . . . . 6 TABLES Table 1 Relay contact card pin configuration. . . . . 4 Table 2 Jumper connections . . . . . . . . . . . . . . . . . .
ii
Introduction 1.0 INTRODUCTION The Liebert Intellislot™ Interface for Relay Contacts card provides contact closures for remote monitoring of alarm conditions in your Liebert UPS. Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS signals, the easy-to-install card integrates with other relay contact monitoring systems.
Installation 2.0 INSTALLATION Parts and Tools Required • Intellislot Interface for Relay Contacts card and required cable assembly • #2 (medium) Phillips or small flat-head screwdriver Instructions INTELLISLOT 1. Turning off the UPS prior to installation PORT ON A UPS is suggested, although not required. 2. Locate the Intellislot port on the UPS. The Intellislot port is on the rear of some units (GXT, Nfinity and PowerSure PSI); on the Liebert NX, the port is inside the front door.
Installation 6. Select either interface Option 1 or 2 below (also see Step 7 and 3.0 - Pin Configuration). Option 1: Hardwire (terminal block pins) - Use these guidelines for terminal block specifications: Acceptable Wire Size Wire Strip Length Recommended Tightening Torque 30-16 AWG 0.24-0.28 in. (6-7mm) 1.73 lb-in (2 kgf-cm) Option 2: DB25 pins Screw M2 Remove a. Disconnect the Hardwire screws Adapter board by removing the two mounting screws, as shown at right. Hardwire b.
Pin Configuration 3.
Jumper Setup 4.0 JUMPER SETUP Refer to Table 2 and the figure below for jumper setup. Table 2 Jumper connections # Connection JP01 Pin 9 to Pin 17 Allows all relay COMMONS to be tied together. Pin 7 to Pin 17 Allows all relay COMMONS and the ANY MODE SHUTDOWN GROUND to be tied together. NOTE: This jumper should be removed if there is any external voltage source that may intentionally or inadvertently be connected to the DB25 pins.
Contacting Technical Support 5.0 CONTACTING TECHNICAL SUPPORT Liebert has a team of specially trained technicians waiting to quickly assist you with any installation or troubleshooting problems. Refer to the back of this manual for the Technical Support phone number. To successfully diagnose your individual problem, our technicians may require the following installation site and system information. Please have it available when you call.