User manual

Specifications
25 Liebert
®
InteleCool
2
Table 8 Technical data, 50 Hz - Standard ambient condenser
Model ET035
Compressor type Scroll
Net capacity data based on 26.6°C (80°F) DB/19.4°C (67°F) WB indoor ambient - kW (BTUH)*
Outdoor ambient
29.4°C (85°F)
Total 8.3 (28200)
Sensible 6.2 (21300)
35.0°C (95°F)
Total 7.8 (26600)
Sensible 6.1 (20700)
40.6°C (105°F) **
Total 7.3 (24900)
Sensible 5.9 (20000)
Net capacity data based on 23.9°C (75°F) DB 16.9°C (62.5°F) WB indoor ambient - kW (BTUH)*
Outdoor ambient
29.4°C (85°F)
Total 7.7 (26200)
Sensible 6.2 (21000)
35.0°C (95°F)
Total 7.2 (24700)
Sensible 6.0 (20400)
40.6°C (105°F) **
Total 6.8 (23300)
Sensible 5.8 (19700)
Evaporator Air Flow - Dry Coil
External Static Pressure CFM (m
3
/hr)
0.0 Pa (0.0 - IN WG) 1080m (1840)
25 Pa (0.1 - IN WG) 1020 (1730)
50 Pa (0.2 - IN WG) 940 (1600)
75 Pa (0.3 - IN WG) 860 (1460)
100 Pa (0.4 - IN WG)
125 Pa (0.5 - IN WG)
Evaporator Air Flow - Wet Coil
External Static Pressure CFM (m
3
/hr)
0.0 Pa (0.0 - IN WG) 1000 (1700)
25 Pa (0.1 - IN WG) 930 (1590)
50 Pa (0.2 - IN WG) 860 (1460)
75 Pa (0.3 - IN WG) 780 (1330)
100 Pa (0.4 - IN WG)
125 Pa (0.5 - IN WG)
Evaporator
Motor kW (hp) 0.19 (0.25)
Filter Sizes - Quantity, cm (in.)
16 x 32.5 x 2 - one
(40.6 x 82.5 x 5)
Drain Connection - ID, in. 3/4 (1.9)
Weight - w/o Economizer, kg (Ib) 150 (330)
Weight - with Economizer, kg (Ib) 159 (350)
* Based on rated airflow at 50 Pa (0.2 IN WG) external static and no outside air.
** Use high ambient option for high ambients.