User manual
Installation
7Liebert
®
InteleCool
™
2
6. With the unit front panel removed, lift the unit onto the base angle, making certain that the rear
unit angle falls behind the turned-up front edge of the mounting angle. Insert top and side unit
fasteners in holes and tighten, drawing the unit into place.
7. Verify that all mounting fasteners are properly installed and tightened according to the
structural engineer’s recommendation.
Do not attach ducts to unit prior to installing unit.
8. Caulk and flash the top and sides as required to form a watertight seal. Emerson recommends
using top flashing (field-supplied) to ensure that water does not run behind unit. All unit tops are
sloped to allow water to run off.
Figure 1 Unit mounting dimensions
!
WARNING
Risk of improper handling of heavy unit—330-490 lb. (150-222kg). Can cause injury or death.
Use caution, OSHA recommended safe lifting practices and lifting equipment that is rated for
the unit weight to place the unit on the base angle. See Tables 6-13 for unit weights.
Table 1 Mounting dimensions
Liebert InteleCool2 dimensional data in. (mm)
Model Size Wf A B C D E F G H J K L M N P
2 Ton
38-3/4
(984)
20
(508)
20
(508)
9-3/8
(238)
9-13/32
(239)
8
(203)
20-3/4
(527)
12
(305)
25-1/16
(638)
5-15/32
(139)
12
(305)
3-25/32
(96)
4-1/2
(114)
37-7/8
(962)
2-15/32
(63)
3 Ton
38-3/4
(984)
28
(711)
28
(711)
5-3/8
(137)
5-3/8
(137)
8
(203)
18
(457)
14
(356)
26
(660)
5-15/32
(139)
12
(305)
3-25/32
(96)
4-1/2
(114)
37-7/8
(962)
2-15/32
(63)
4-5 Ton
42-3/4
(1086)
30-1/4
(768)
29-7/8
(759)
6-1/4
(159)
6-7/16
(164)
9-7/8
(251)
30
(762)
15-7/8
(403)
25-25/64
(645)
1-45/64
(43)
16
(406)
61/64
(24)
6-1/2
(165)
41-3/4
(1060)
4-3/8
(111)
See Table 1 below for
keys to dimensions.
G
H
M ref.
N
Wf
K
C
K
K
K
K
A
P
E
J
L
11"
(279mm)
11"
(279mm)
11"
(279mm)
DB
F