User manual

Operation
Liebert
®
iCOM
®
for Liebert DSE
40
Dehumidification Operation
Dehumidification with four compressors operates until there is a call for the first stage reheat.
Dehumidification with three compressors operates until there is a call for the second stage reheat
or LL1 is reached
Dehumidification with two compressors is allowed to operate with full reheats until the LL2
threshold is met
Digital compressors will operate when the unit is in 2 compressor dehum operation.
This allows the outer coil to precool the air which makes the inner coil more effective for
dehumidification.
If there are compressor alarms, the unit will adjust the compressor dehumidification operation
until three of the four compressors are unavailable.
Compressors C1A, C1B, C2A, and C2B must be ON.
The C1A Digital Compressor must be loaded at 100% at all times.
The C2A Digital Compressor will adjust its loading based on whether the call for
dehumidification (CFD) is greater than the call for cooling (CFC): If the call for
dehumidification (CFD) is greater than or equal to the CFC, C2A must use the ramp on line DH05
(“C2A CFC @ 0% / 100% Dehum Ramp”), with the CFD value used to determine ramp %. If the
CFD is less than the CFC, then C2A must use the ramp on line DH06 (“C2A CFC @ 0% / 100%
Cooling Ramp”), with the call for cooling value used to determine ramp %.
If a reheat stage greater than or equal to the stage on the left-hand side of line DH07 becomes
active, the C1B compressor must be turned Off. Once this happens, control operation moves to DH
Stage 2.
If the Low Limit Sensor (Line S132) temperature becomes less than or equal to the Low Limit 1
border (lines S132 & S133, the C2B and C1B compressors must be turned Off. Once this happens,
control operation moves to DH Stage 1.
Dehumidification with Three Compressors (DH Stage 2)
Compressors C1A, C2A, and C2B must be On, and C1B must be Off.
The C1A Digital Compressor must be loaded at 100% at all times.
The C2A Digital Compressor will adjust its loading based on whether the Call for
Dehumidification (CFD) is greater than the Call for Cooling (CFC): If the CFD is greater than or
equal to the CFC, C2A must use the ramp on line DH05 (“C2A CFC @ 0% / 100% Dehum Ramp”),
with the CFD value used to determine ramp %. If the CFD is less than the CFC, then C2A must
use the ramp on line DH06 (“C2A CFC @ 0% / 100% Cooling Ramp”), with the call for cooling
value used to determine ramp %.
If the reheat stage indicated on the right-hand side of line DH07 becomes active, the C2B
compressor must be turned OFF. Once this happens, control operation moves to DH Stage 1.
If the Low Limit Sensor (line S132) temperature becomes less than or equal to the Low Limit 1
border (lines S132 & S133), the C2B compressor must be turned OFF. Once this happens, control
operation moves to DH Stage 1.
If a reheat greater than or equal to the stage indicated on the left-hand side of line DH07 is
inactive, and the Low Limit sensor (line S132) temperature is above the Low Limit 1 reset border,
then Compressor C1B can start (or restart) if the CFC becomes greater than or equal to the value
on line DH02 (“C1B Start @ CFC”). Operation then moves to DH Stage 3.