User manual

Operation
37 Liebert
®
iCOM
®
for Liebert DSE
Dehumidification Low Limit
Figure 28 Setpoints screen, page 3 of 9
Figure 29 Dehumidification and reheat control bands
NOTE
When the unit is in relative humidity control, only the right side of the menu is displayed and
dew point will display the left side of the menu.
Dehum Reheat Prop Band
-100%
-Temp
33% 33% 33%
Step 3 Step 2
Step 3 on
Step 3 off
Step 2 on
Step 2 off
Step 1 on
Step 1 off
0%
Dehum / Reheat
Setpoint
0%
Heater
Deadband
Step 1
Dehum Reheat Prop Band
0%
Dehum / Reheat
Setpoint
-100 %
-Temp
33% 33% 33%
Step 3 Step 2
Step 3 on
Step 3 off
Step 2 on
Step 2 off
Step 1 on
Step 1 off
Step 1