2.0 LIEBERT ICOM DISPLAY COMPONENTS AND FUNCTIONS
The large display has the layout shown in Figure 2.
Figure 2 Liebert iCOM display components
NOTICE
Risk of inadvertent system shutdown. Can cause loss of cooling and equipment damage.
Pressing the On/Off key on a Liebert iCOM large display while the system screen is shown
permits shutting down all units on the network.
Large Liebert iCOM displays can view and control other units on the network when they are
in the same group. When turning a unit Off or On with the large display, make sure that the
unit to be shut down or started up is shown on the screen. If the system screen is shown and
the On/Off key is pressed, the Liebert iCOM shows a notification that pressing the On/Off key
again will turn off all units on the network.
NOTE
The Help key may be pressed at any time for a brief explanation of what is being viewed.
ESC
?
Liquid Crystal Display
Keypad
LED Status Indicators
(top LED is red or
flashing red; bottom
LED is green or amber)
ESC
?
On/Off Key
Escape Key Down Arrow Key
Up Arrow Key
Left Arrow Key Right Arrow KeyEnter Key
Alarm Key
Help Key