Unit installation

Electrical Connections
45
Positioning the 2T Sensor Rack Probes on a Rack
To help ensure proper cooling, use the following guidelines to place the Liebert 2T sensor probes:
on the top of the perforated rack door.
in front of the highest-mounted servers in the rack.
in front of the highest-density area of the rack.
in the airflow path entering the rack.
Do not place the probe directly on the metal surface of the perforated door.
To connect the temperature probes, use only cable with the following characteristics:
6 wires, 3 couples, shielded twisted pair
termination: RJ-12
coupling: according to Liebert iCOM user manual, SL-18835)
Option A:
3 x 2 x 0.14 mmq (min), twisted pairs, shielded
plenum rated
300V
(23/158
°F / -5/+70°C)
•flexible
characteristic impedance of 108-132 Ohm @50kHz
conductor resistance < 150 Ohm/km
•flame-retardant
black jacketing
Option B:
•24AWG
STP (Shielded Twisted Pair)
CMP (plenum rated)
<15pF capacitance per foot
300V
•140
°F / 60°C
black jacketing
flexibility: must maintain a certain, unspecified flexibility
UL and CSA approved