Unit installation
Liebert iCOM Control
24
5.4 Liebert iCOM Control Setup
The Liebert iCOM on the Liebert CRV leaves the factory with the fan speed and cooling capacity con-
trolled by the supply air sensor. This control mode is extremely robust and will ensure that you are
delivering precise cooling to the cold aisle. To unlock the full capability of the Liebert CRV, the remote
rack sensors should be installed, which will allow the fan speed and the cooling capacity to be “de-cou-
pled.” This means that the fan speed can now be controlled independently of the cooling capacity. In
this advanced configuration, the Liebert CRV can control the discharge temperature of the unit by
modulating cooling capacity based on the supply sensor and use the remote rack sensors to ensure
that the cool air is being delivered to the inlet of the racks. Using the supply and remote rack sensors
in this de-coupled mode is the preferred method for controlling the Liebert CRV in a hot / cold aisle
configuration. In addition to this configuration Emerson has provided additional flexibility for other
applications shown in Table 7.
Figure 24 Setpoint screen
In Figure 24, the controlling sensor can be selected for the different types of sensor control modes. As
the selection is changed from one sensor to another, the setpoint value moves to the appropriate sen-
sor position, giving a visual indication of the sensor placement in relationship to the Liebert CRV.
Table 7 shows the flexibility of the Liebert CRV and how the different sensor configurations can be
used to control the Liebert CRV fan speed and cooling capacity. The table shows the different coupled
and decoupled modes available for the Liebert CRV.
Table 7 Controlling sensor settings
Cooling Control
S103Cool / S125 Fan Supply Remote Sensor Return
Fan Control
Supply
Factory Default
(Coupled)
N/A N/A
Remote Sensor
Recommended
(Decoupled)
X
(Coupled)
N/A
Return
X
(Decoupled)
X
(Decoupled)
X
(Coupled)