5.3.2 Remote Rack Sensor Operation and Rack View Setup
Figure 20 Rack setup screen, page 1 of 3
Once the remote rack sensors have been configured and plugged into the CAN bus network, the con-
trol can be configured to use the sensor for either control or reference. If the sensor is set to “Disable,”
it will be ignored. The sensor node number corresponds to the DIP switch assignment of the sensor.
Figure 21 Rack setup screen, page 2 of 3
Once a sensor has been assigned to either control or display its temperature data a virtual position
can then be assigned to the sensor. This screen configures the Rack View layout in the User menu.
This step is not required for the sensor to operate but does provide a logical position in the row for
quickly referencing affected racks near the Liebert CRV. To set up navigate using the arrow and enter
keys to highlight the Assign Sensors number range. Once the range is selected then press the enter
key to move to the rack location blocks at the bottom of the screen. The Up and Down arrow keys can
be used to select the sensor node number. For the Liebert CRV select “CRV.”