User manual
Service Menu Parameters
89
Figure 81 System/Network setup parametersUnit - Page 2
Monitoring Protocol—This parameter selects the monitoring protocol. Velocity V3 is the factory
default which will provide communications to the Intellislot housing. iGMNet will activate the 77/78
terminals for communications to the SiteLink(-E). Hironet is only used on HPM units.
IP Address—This parameter contains the network address of the display. This address must be
unique to every other device on the network.
Netmask—Not currently used.
Gateway—Not currently used.
MAC—The MAC address is a unique hardware identifier of the Ethernet device.
U2U Protocol—This parameter is always set to GBP.
U2U Address—This parameter is a unique identifier for each unit on the network. Display addresses
range from 33 to 64. Each display on the U2U network must have a different U2U address.
U2U Group—This parameter is used to create zones or groups within a U2U network. Once a group
number is selected the display will only see other devices with the same group number. The group
number can be changed to view other devices in different groups.
Bootloader Variables—This parameter indicates if there has been a change to the boot loader since
it was last loaded. This parameter should only be activated by an authorized service person.
Attention: any changes done on these parameters
must be followed by a 'Save+Reboot' command.
SYSTEM/NETWORK SETUP (page 2 of 2) UNIT 01
S834
S835
S836
S837
S838
S839
S840
S841
S842
S843
S844
PASSWORD (Actual Level 3) ????
Monitoring Protocol Velocity
IP Address 192 .168.254.001
Netmask 255 .255.255.000
Gateway 0:000:000:000
MAC 00:00:68:1E:8E:92
U2U Protocol GBP
U2U Address 1
U2U Group 1
Bootloader Variables Changed No
Static RAM OK No