Service Menu Parameters
84
Figure 74 iCOM-DO Events Setup - Page 3
Figure 75 Sensor calibration / setup parameters - Page 1
Return Temperature—This parameter adjusts the return temperature reading from the actual
sensor to compensate for any error of the sensor or to match other sensors in the room.
Calibrated Return Temperature—This parameter shows the adjusted temperature value of the
return sensor. This value is the actual sensor reading (+ or -) the offset “Return Temperature”.
Return Humidity—This parameter adjusts the return humidity reading from the actual sensor to
compensate for any error of the sensor or to match other sensors in the room.
Calibrated Return Humidity—This parameter shows the adjusted humidity value of the return
sensor. This value is the actual sensor reading (+ or -) the offset “Return Humidity”.
Digital Scroll 1 NTC—This parameter adjusts the digital scroll 1 NTC reading from the actual sen-
sor to compensate for any error or drift of the sensor.
Calibrated Digital Scroll 1 NTC—This parameter shows the adjusted Digital Scroll 1 NTC sensor
value. This value is the actual sensor reading (+ or -) the offset “Digital Scroll 1 NTC”.