User manual
Service Menu Parameters
81
Type—This selection sets the type of action for each event listed. There are 3 different types of events
(Alarm, Warning and Message). When an event is triggered and the type is set to alarm then the light
and buzzer on the Display will activate, an event will be written to the event log and the (K3) alarm
relay will close. If the type is set to Warning then the light and buzzer on the display will activate, an
event will be written to the event log and the (K3) alarm relay can be configured to close or provide no
reaction. If the type is set to Message, then the event is only written to the event log.
Figure 68 Set alarms parameters screen - Page 4
Figure 69 Set alarms parameters screen - Page 5
SET ALARMS (page 4 of 7)
PASSWORD (Actual Level 0) ????
DELAY EN-DIS TYPE
COMP 1 OVERLOAD ENABLE ALM
COMP 2 OVERLOAD ENABLE ALM
COMP 1 HIGH PRESSURE ENABLE ALM
COMP 2 HIGH PRESSURE ENABLE ALM
COMP 1 LOW PRESSURE ENABLE ALM
COMP 2 LOW PRESSURE ENABLE ALM
COMP 1 PUMPDOWN FAIL ENABLE ALM
COMP 2 PUMPDOWN FAIL ENABLE ALM
DIGI SCROLL1 HIGH TEMP ENABLE ALM
DIGI SCROLL2 HIGH TEMP ENABLE ALM
EL HEAT HIGH TEMP 5 ENABLE WRN
S236
S237
S238
S239
S240
S241
S242
S243
S244
S245
S246
S247
S248
UNIT 01
SET ALARMS (page 5 of 7)
PASSWORD (Actual Level 0) ????
DELAY EN-DIS TYPE
WORKING HRS EXCEEDED 0 ENABLE WRN
SMOKE DETECTED 2 ENABLE ALM
WATER UNDER FLOOR 2 ENABLE ALM
COND PUMP-HIGH WATER 2 ENABLE ALM
LOSS OF FLOW 5 ENABLE ALM
STBY PUMP ON 2 ENABLE ALM
STANDBY UNIT ON 2 ENABLE ALM
HUMIDIFIER PROBLEM 2 ENABLE ALM
NO CONNECTION w/Unit1 ENABLE WRN
UNIT X DISCONNECTED ENABLE WRN
LOSS OF POWER DISAB WRN
S249
S250
S251
S252
S253
S254
S255
S256
S257
S258
S259
S260
S261
UNIT 01