User manual

Service Menu Parameters
68
Figure 50 Wellness basic settings screen- Page 1
Maximum Frequency Per year—This parameter sets the number of expected maintenance visits
in a one year time span.
Max Bonus—This parameter will increase the time to the next maintenance cycle. A bonus should be
assigned when a service visit finds that all components are working optimally.
Max Penalty—This parameter will decrease the time to the next maintenance cycle. A penalty
should be used when a service visit finds excessive wear on components.
Last Maintenance—This parameter is set during the service call. It also indicates to other service
personnel the date of the last visit.
Service Engineer—This parameter provides a label for the service representative to list either the
company name or representative’s name.
Confirm PM—This parameter confirms that the service representative has completed the preventive
maintenance and resets the next maintenance date.
Calculated Next Maintenance—This parameter provides a date to when the next expected mainte-
nance should take place based on the last confirmed PM, component starts, run hours and the
penalty / bonus currently set in the Liebert iCOM control.