Installing a Liebert iCOM Unit-to-Unit Network
45
5.2 U2U Hardware: Cables and Network Switch
Plan wiring runs for U2U communication when designing the layout of your conditioned space. In
addition to general good wiring practices, take into account:
Ethernet CAT5 or greater cable is required for interconnecting the units.
Maximum distance must not exceed 328 feet (100m).
A device to boost the Ethernet signal may be used to exceed the 328 feet (100m) length limitation.
Ethernet network should be private—set up only for management and control of the cooling units.
Keep control and communication cables away from power cables to prevent electromagnetic inter-
ference.
Do not bend cables to less than four times the diameter of the cable.
Do not deform cables when securing in bundles or when hanging them.
Keep cables away from devices that can introduce noise into them, such as machines, fluorescent
lights, and electronics.
Avoid stretching Ethernet cables—tension when pulling cables should not exceed 25 pounds
(11kg).
Do not secure Ethernet cables with any method that might damage them; use approved hangers,
such as telephone wire/RG-6 coaxial wire hangers, available at most hardware stores.
Minimum Network Switch Requirements
IEEE 802.3; IEEE 802.3u
10/100 Mbps speed
Multiple 10/100 RJ-45 ports—one shared; RJ-45 Uplink port
The Liebert vNSA
is an approved powered network switch designed to support Liebert iCOM U2U
networks. See Liebert vNSA on page 50 for details.