Outputs - Status and Alarms
5
4.0 OUTPUTS - STATUS AND ALARMS
A three-position screw terminal block is provided for each
Form-C contact closure output. The wiring connection is uni-
form for all 16 outputs:
Position 1: Common
Position 2: Normally Closed
Position 3: Normally Open
Position 1 is the left-most connection, and is marked by a tri-
angular symbol on the circuit board. The outputs are not
supervised (except as noted below); thus, the N.O. contact
would be closed only upon an active/alarm condition.
Refer to Table 3 for the standard mapping of status and
alarms. The output terminal block (TB) for each alarm output
is configurable. For details, refer to the Liebert iCOM manual,
SL-18835, available at Liebert’s Web site: www.liebert.com
NOTE
The top of the screw terminals cannot be used to obtain
contact when using a meter to verify the status of a contact
closure. The meter must contact the terminal block in the
openings where the wires are inserted.
Table 3 Standard mapping of status and alarms
Terminal Block Description Liebert iCOM
TB1 Cooling Status
TB2 Heating Status
TB3 Humidifying Status
TB4 Dehumidifying Status
TB5 High Temperature
TB6 High Humidity
TB7 Low Temperature
TB8 Low Humidity
TB9a High Head Pressure C1
TB9b High Head Pressure C2
TB10 Loss of Airflow
TB11 Change Filters
TB12 Water Detected/Customer Alarm 1
TB13 Customer Alarm 2
TB14 GLYCOOL Status
TB15 Unit On