1.0 INTRODUCTION
The Liebert iCOM Discrete Output interface card provides dis-
crete outputs for Liebert Precision Cooling units equipped
with a Liebert iCOM control. Operating status is monitored
and critical alarms are communicated via contact closure. Any
alarm monitor, I/O panel, autodialer or monitoring system can
be used to monitor your Liebert unit.
The Liebert iCOM-DO card is available as a factory-installed
option or in a kit for field-retrofit to Liebert Precision Cooling
units equipped with the Liebert iCOM control.
Figure 1 Typical system configuration
Table 1 Specifications
Electrical Requirements
Voltage 24VAC or 24VDC, ±20% 50/60 Hz, Single Phase
Power 10W maximum
Environmental Conditions, °C (F)
Operating
Temp.
5 to 55 (41 to 131)
Storage Temp. -20 to 70 (-4 to 158)
Humidity: 10% to 95% RH (non-condensing)
Dimensions, mm (inches)
Card Only 178 x 102 x 38 (7.0 x 4.0 x 1.5)
Shipping 248 x 178 x 64 (9.75 x 7.0 x 2.5)
Weight, kg (lb)
Net 0.1 (0.2)
Shipping 0.6 (1.3)
Compatibility
Precision Cooling units with Liebert iCOM control and
software version # PA1.04.022 STD or newer
Discrete
Outputs
16 Form-C Contact Closures (SPDT Relays, energize to alarm)
Rating: 1A @ 30VDC; 0.46A @ 65 VDC; 0.46 A @ 150VAC
16-24 AWG (1.5mm
2
- 0.25mm
2
)wiring
Dry-Contact Discrete Outputs to:
• BMS Interface
• Alarm Panel
• Autodialer , etc.
2-Wire Connection Per Alarm
Liebert Precision Cooling Unit
Liebert iCOM-DO
Interface Card