User manual

Table Of Contents
Operating Instructions
38
The following metering parameters may be displayed:
Voltage - Line-to-Line
Voltage - Line-to-Neutral
Neutral Current
Ground Current
•kVA
Power Factor
Voltage Total Harmonic Distortion (THD)
Current Total Harmonic Distortion (THD)
Crest Factor
Circuit identification and status of each breaker may be displayed.
The Liebert LDMF detects and annunciates by alarm message the following conditions:
•Overvoltage
Undervoltage
Neutral Overcurrent
Ground Overcurrent
Phase Overcurrent
Phase Overcurrent Warning
Summary Alarm
All alarm thresholds for monitored parameters are adjustable by way of the LDMF DB-9 setup port to
match site requirements. The factory setpoints for the alarms are as follows:
Overvoltage - at least one of the line-to-line voltages exceeds +6% of nominal
Undervoltage - at least one of the line-to-line or line-to-neutral voltages falls below -13% of
nominal
Phase Overcurrent Warning - current exceeds 75% of breaker amps
Phase Overcurrent - current exceeds 80% of breaker amps
Neutral Current - current exceeds 95% of breaker amps
Ground Current - current exceeds 5 amps
Summary Alarm
Summary Alarm - detects and annunciates any alarm.
Summary Alarm Contacts
The LDMF has a form C (one NO and one NC) summary alarm contacts for remote alarm status.
The contacts are rated at 24VAC @ 1A. There is one alarm contact per breaker. The contacts
change state upon occurrence of any alarm including warnings and resets when the alarm is
cleared. Summary alarm contacts are located on the adapter board. The adapter board is located
on top of the monitoring enclosure. See Figure 15 for details.
Communication - Liebert IntelliSlot cards provide customer connections to a Building Management
System (BMS) or Remote Monitoring Systems. The following cards are available:
IS-WEBS Card - Provides SNMP/WEB output. An RJ-45 connector is supplied for customer
connection to Ethernet LAN.
IS-485S Card - Provides Modbus 485 output. A terminal strip is provided for 2-wire connection.
IS-IPBMS Card - Provides Modbus IP output. An RJ-45 connector is supplied for customer
connection.
Up to three cards can be plugged into the Liebert IntelliSlot ports provided with the Liebert LDMF
system.
If communication to Liebert SiteScan is required, customer connection can be made to the adapter
board RS-485 terminals on TB1, see Figure 15 for details. The adapter board is located on top of the
monitoring enclosure.