User's Manual

Specifications
Liebert
®
DCP
70
9.0 SPECIFICATIONS
Table 5 Liebert DCP200 specifications
Models
DCP200RA2BB0 DCP200RM2BB0
Cooling Capacity, Nominal
200kW / 57 Tons, 60Hz 200kW / 57 Tons, 50Hz
Each capacity is based on 45ºF (7ºC) entering water temperature
and 114 gpm (26 m
3
/h) water flow rate. Capacity is reduced when
glycol mixtures are used in place of 100% water.
Electrical Requirements
Input 460V/3/ph60Hz 380/415V/3ph/50Hz
Full Load Amps 7.3A 8.7A
WSA
1
8 9
MFCB
2
15 15
Dimensions, inches (mm)
Height – Unit Only 78 (1981)
Height – As Shipped 83 (2108)
Width 38 (965)
Depth 34 (864)
Weight, lb (kg)
Unit Only 931(423) 1105 (502)
Shipping Weight 1100 (499) 1275 (579)
Installed, with Fluid and Chilled Water 1148 (521) 1322 (600)
Pipe Connections
Fluid Supply to Cooling Module 2-5/8" OD, Cu
Fluid Return from Cooling Module 2-5/8" OD, Cu
Chilled Water Supply and Return 2-5/8" OD, Cu
Control Valve
2-way, 2" nominal; 35 PSIG close-off pressure rating;
150 PSIG maximum allowable pressure
Pressure Drop – Chilled Water Side
14.0 psig (97kPa, 0.97bar), with 114 gpm (26 m
3
/h) water flow rate,
control valve fully open
Temperature Rise – Chilled Water Side
at Rated Flow, °F (°C)
12.0 (6.7)
Number of Liebert Cooling Units Connected, Maximum
Liebert DCD35 10 @ 20 kW
Cabinet Exterior Finish Black, matte finish, heat-fused powder coat
Operating Ambient
Temperature, Maximum, °F (°C)
86 (30)
1. WSA = Wire Sizing Amps (Minimum supply circuit ampacity)
2. MFCB = Maximum Fuse or Circuit Breaker Size