User's Manual
Liebert iCOM
®
Control—Firmware Version XP1.00.DCP.01R
Liebert
®
DCP
™
58
Netmask—Defines which part of the IP address is used for the network. The factory default is
255.255.255.000.
Gateway—A network point that acts as an entrance to another network. The factory default is
0.000.000.000.
MAC—A unique hardware identifier for the Ethernet device. The following parameters (U2U
Protocol, U2U Address and U2U Group) are for displaying other networked Liebert
DCP units. The
Liebert DCP does not perform Teamwork Operations.
U2U Protocol—This is always set to GBP.
U2U Address—A unique identifier for each display on the network. Display addresses range from 33
to 64. Each display on the U2U network must have a different U2U address. Not currently used.
U2U Group—Used to create zones or groups within a U2U network. Once a group number is
selected, the display will see only other devices with the same group number. The group number can
be changed to view other devices in different groups. Not currently used.
Bootloader Variables—Indicates the bootloader has changed since it was last loaded. This
parameter should only be activated by an authorized service person.
Figure 66 System/Network Setup screen—Unit, page 1 of 2
Monitoring Address—Sets the address used by the Liebert IntelliSlot
®
cards. This is set to 3 at the
factory and should not be changed.
Unit Name—Identifies the unit from the local or remote display. This label will show at the top right
of every screen that has monitoring or configuration of that unit
Configuration Safe—Saves or loads configuration settings for the control board that have been
modified from the factory defaults to an internal file that can be downloaded / uploaded using the
Liebert iCOM
®
Service Tool. Selecting “Save” will write the settings to the internal storage file and
selecting “Load” will write the settings from the internal storage file to the application software. The
internal file is updated every 12 hours automatically.
Network Safe—Saves or loads network settings for the control board that have been modified from
the factory defaults to an internal file that can be downloaded / uploaded using the Liebert iCOM
Service Tool. Selecting “Save” will write the settings to the internal storage file and selecting “Load”
will write the settings from the internal storage file to the application software.
SW Version—Contains the application software version loaded onto the Liebert iCOM.
SYSTEM/NETWORK SETUP (page 1 of 2)
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSWORD (Actual Level 0)
Monitoring Address
Unit Name
Configuration Safe
Network Safe
SW Verson
S823
S824
S825
S826
S827
S828
S829
S830
S831
S832
S833
????
3
UNIT
No
No
OK
OK
XP1.00.008.STD
UNIT 01