Figure 62 Sensor Calibration/Setup screen, page 2 of 3
Supply Coolant Sensor—Adjusts the temperature reading from the actual supply coolant sensor to
compensate for any error of the sensor.
Calibrated Supply Coolant Sensor—Displays the adjusted temperature value of the supply
coolant sensor. This value is the actual sensor reading plus or minus the offset Supply Coolant
Sensor.
Supply Chilled Water Sensor—Adjusts the temperature reading from the actual supply chilled
water sensor to compensate for any error of the sensor.
Calibrated Chilled Water Sensor—Displays the adjusted temperature value of the supply chilled
water sensor. This value is the actual sensor reading plus or minus the offset Supply Chilled Water
Sensor.
Figure 63 Sensor Calibration/Setup screen, page 3 of 3
Supply Coolant Sensor 0%—Allows the sensor reading to be calibrated at the lowest reading of the
sensor. This calibration changes the start point of the sensor reading.
Supply Coolant Sensor 100%—Allows the sensor reading to be calibrated at the highest reading of
the sensor. This calibration changes the end point of the sensor reading.
SENSOR CALIBRATION/SETUP (page 2 of 3) UNIT 01
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSWORD (Actual Level 0)
Supply Coolant Sensor
Calibrated Supply Coolant Sensor
Supply Chilled Water Sensor
Calibrated Supply Chilled Water Sensor
S612
S613
S614
S615
S616
S617
S618
S619
S620
S621
S622
????
+0.0°F
58.5°F
+0.0°F
60.1°F
SENSOR CALIBRATION/SETUP (page 3 of 3) UNIT 01
PASSWORD (Actual Level 0)
Supply Coolant Sensor 0%
Supply Coolant Sensor 100%
S623
S624
S625
S626
S627
S628
S629
S630
S631
S632
S633
????
30.0°F
90.0°F
to confirm
for next/previous unit
then
to select parameter
to change parameter