WATER UNDER FLOOR—Enables or disables the Water Under Floor event, which occurs when
the Customer Input 1 is configured for “Water Under Floor” and 24VAC is applied to the input. Sets
how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits
before reporting the event.
UNIT X DISCONNECTED—Not currently used.
WORKING HOURS EXCEEDED—Enables or disables the Working Hrs Exceeded event, which
occurs when a component has exceeded the user-specified limit. Sets how the event is reported: as an
alarm, a warning or a message. Specifies how long the control waits before reporting the event.
CALL SERVICE—Enables or disables the Call Service event, which occurs when the Customer
Input 1 is configured for “Call Service” and 24VAC is applied to the input. Sets how the event is
reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting
the event.
LOSS OF POWER—Enables or disables the Loss of Power event, which occurs when the unit is On
and operational and the 24VAC power to the control is lost. Sets how the event is reported: as an
alarm, a warning or a message. Specifies how long the control waits before reporting the event.