User's Manual

Liebert iCOM
®
Control—Firmware Version XP1.00.DCP.01R
49 Liebert
®
DCP
Figure 55 Set Alarms screen, page 1 of 7
High Room Air Temperature—Sets the threshold for a high room air temperature alarm. The
range for the high room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F
(26.7°C).
Low Room Air Temperature—Sets the threshold for a low room air temperature alarm. The range
for the low room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 55°F (12.8°C).
High Room Dewpoint—Sets the threshold for a return high dew point alarm. The range for the
high room dew point alarm is from 33.8 to 95°F (1 to 35°C); the default is 65°F (18.3°C).
High Coolant Temperature—Sets the threshold for a high a coolant temperature alarm. The range
for the high supply coolant temperature alarm is from 33.8 to 122°F (1 to 50°C); the default is 80°F
(26.7°C).
High Chilled Water Temperature—Sets the threshold chilled water temperature for a supply high
chilled water temperature alarm. The range for the high supply fluid temperature alarm is from
33.8
to 113°F (1 to 45°C); the default is 60°F (15.6°C).
SET ALARMS (page 1 of 7) UNIT 01
S201
S202
S203
S204
S205
S206
S207
S208
S209
S210
S211
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSWORD (Actual Level 0) ????
High Room Air Temperature 88.F
Low Room Air Temperature 55.F
High Room Dewpoint 65.F
High Coolant Temperature 80.F
High Chilled Water Temperature 60.F