User's Manual
Liebert iCOM
®
Control—Firmware Version XP1.00.DCP.01R
47 Liebert
®
DCP
™
Figure 52 Diagnostics/Service Mode screen, page 4 of 6
Manual Mode Control Type—Not currently used.
Manual Deviation—Not currently used.
Analog Output Ramp 1—Sets the value of Analog Output 1 value as a percentage. The factory
default for the Liebert DCP is the Valve Percent Open.
Analog Output Ramp 2—Sets the value of Analog Output 2 value as a percentage. The factory
default for the Liebert DCP is the Call for Cooling.
Analog Output Ramp 3—Sets the value of Analog Output 3 value as a percentage. The factory
default for the Liebert DCP is the CW Temp.
Analog Output Ramp 4—Sets the value of Analog Output 4 value as a percentage. The factory
default for the Liebert DCP is the coolant temperature.
Alarm Relay—Used to activate the Liebert iCOM
®
common alarm relay output.
Warning Relay—Used to activate the Liebert iCOM’s warning relay output.
Figure 53 Diagnostics/Service Mode screen, page 5 of 6
DIAGNOSTICS/SERVICE MODE (page 4 of 6) UNIT 01
S334
S335
S336
S337
S338
S339
S340
S341
S342
S343
S344
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSWORD (Actual Level 0) ????
Manual Mode Control Type Full
Manual Deviation 12%
Analog Output Ramp 1 30%
Analog Output Ramp 2 0%
Analog Output Ramp 3 60%
Analog Output Ramp 4 58%
Alarm Relay Off
Warning Relay Off
DIAGNOSTICS/SERVICE MODE (page 5 of 6) UNIT 01
S345
S346
S347
S348
S349
S350
S351
S352
S353
S354
S355
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSWORD (Actual Level 0) ????
Status Remote Shutdown o–o On
Status Fan Failure o/o Ok
Status Diff Press Switch 1 o/o Act
Status Customer Input 1 o/o Ok
Status Condensation Detect o/o Ok
Status Unit Ready o–o On