User's Manual
Liebert iCOM
®
Control—Firmware Version XP1.00.DCP.01R
41 Liebert
®
DCP
™
Figure 43 Liebert DCP Service Menu screen
4.10 Liebert iCOM
®
Service Menu Screens
Service menus allow customized settings for site operations. Service Menu screens employ a coding
that begins with “S” and is followed by parameters and information, such as settings. Gaining access
to most Service Menus requires entering a password; the Service Menu password is 5010; see
4.3.3 -
Entering the Password for assistance.
The Liebert iCOM firmware is being updated constantly. As a result, the Service Menu parameters in
this manual may be slightly different from what is shown on a cooling unit’s display. Check
www.liebert.com for the latest Liebert iCOM user manual updates.
Figure 44 Setpoints screen
NOTE
Menu shows icons only; text is explanatory and does not appear on the Liebert iCOM display.
SERVICE MENUS
to select parameter
to change level
to open requested menu
ESC
to unselect
to navigate
+
WELLNE S S
SET
ALARMS
SERVICE
+/-
NETWORK
SET
UP
XDIO
°C / °F
% RH
SET
SETPOINTS
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSWORD (Actual Level 0)
Min Room Temperature Setpoint
Temperature Control Type
Temperature Proportional Band
Temperature Integration Tiime
Temperature Derivative
Dewpoint Margin
Minimum Control Point
Min Percent Cooling Setpoint
S101
S102
S103
S104
S105
S106
S107
S108
S109
S110
S111
????
60.0°F
Intelligent
7.0°F
min
sec
4.0°F
50.0°F
10%
UNIT 01