User's Manual
Liebert iCOM
®
Control—Firmware Version XP1.00.DCP.01R
Liebert
®
DCP
™
36
Figure 35 Sensor Data screen, page 2 of 2
Daily High Temperature—Shows the highest temperature in a rolling 24 hour period for either
remote Sensor A or remote Sensor B.
Daily Low Temperature—Shows the lowest temperature in a rolling 24 hour period for either
remote Sensor A or remote Sensor B.
Daily High Humidity—Shows the highest humidity in a rolling 24 hour period for either remote
Sensor A or remote Sensor B.
Daily Low Humidity—Shows the lowest humidity in a rolling 24 period for either remote Sensor A
or remote Sensor B.
Daily High Dew Point—Shows the highest dew point in a rolling 24 hour period for either remote
Sensor A or remote Sensor B.
Daily Low Dew Point—Shows the lowest dew point in a 24 hour period for either remote Sensor A
or remote Sensor B.
Daily High Coolant Temperature—Shows the highest supply coolant temperature in a rolling 24
hour period from the Liebert DCP to the modules.
Daily Low Coolant Temperature—Shows the lowest supply coolant temperature in a rolling 24
hour period from the Liebert DCP to the modules.
Daily High Chilled Water Temperature—Shows the highest chilled water supply temperature
being delivered to the Liebert DCP in a rolling 24 hour period.
Daily Low Chilled Water Temperature—Shows the lowest chilled water return temperature
being delivered to the Liebert DCP in a rolling 24 hour period.
SENSOR DATA (page 2 of 2) UNIT 01
U313
U314
U315
U316
U317
U318
U319
U320
U321
U322
U323
U324
This window is READ ONLY
Daily High Temperature 07:49:57 72°F
Daily Low Temperature 07:11:30 64°F
Daily High Humidity 11:31:46 45%
Daily Low Humidity 07:56:18 34%
Daily High Dew Point 07:47:26 45°F
Daily Low Dew Point 08:02:20 37°F
Daily High Coolant Temp 13:01:25 69°F
Daily Low Coolant Temp 13:01:11 69°F