User's Manual

Liebert iCOM
®
Control—Firmware Version XP1.00.DCP.01R
35 Liebert
®
DCP
Figure 34 Sensor Data screen, page 1 of 2
Sensor A Temperature—Displays the temperature of the remote CAN Temp Humidity sensor
designated as Sensor A.
Sensor A Humidity—Displays the humidity of the remote CAN Temp Humidity sensor designated
as Sensor A.
Sensor A Dew Point—Displays the dew point of the remote CAN Temp Humidity sensor designated
as Sensor A.
Sensor B Temperature—Displays the temperature of the remote CAN Temp Humidity sensor
designated as Sensor B.
Sensor B Humidity—Displays the humidity of the remote CAN Temp Humidity sensor designated
as Sensor B.
Sensor B Dew Point—Displays the dew point of the remote CAN Temp Humidity sensor designated
as Sensor B.
Supply Coolant Temperature—Displays the actual supply coolant temperature from the Liebert
DCP to the modules.
Supply Chilled Water Temperature—Displays the actual the Supply Chilled Water temperature
to the Liebert DCP.
SENSOR DATA (page 1 of 2) UNIT 01
U301
U302
U303
U304
U305
U306
U307
U308
U309
U310
U311
U312
This window is READ ONLY
Sensor A Temperature 62.F
Sensor A Humidity 42.20%
Sensor A Dew Point 39.4°F
Sensor B Temperature 71.F
Sensor B Humidity 29.60°%
Sensor B Dew Point 37.8°F
Supply Coolant Temperature 55.F