User's Manual
Installation
Liebert
®
DCP
™
10
Figure 8 Piping access points
2.2 Electrical Considerations
Make sure the actual supply voltage and frequency correspond to the voltage and frequency indicated
on the Liebert DCP’s rating plate. The unit must be installed in accordance with national wiring
regulations.
Connect cables for high voltage supply to the electrical box in the Liebert DCP according to Figure 11
and make sure that the phases are correctly connected.
!
WARNING
Risk of electric shock. Can cause injury or death.
Open all local and remote electric power supply disconnect switches and verify with a
voltmeter that power is Off before working within the unit’s electrical connection enclosures.
!
WARNING
Risk of electrical shock, short circuit and/or control malfunction. Can cause equipment
damage, injury or death.
Damage to wiring or components can make unit unsafe to operate.
Use caution when installing wiring to prevent damage to factory wiring.
Install protective bushings in wiring knockouts as required to protect wiring from sharp
edges.
Do not disturb factory wiring or route field-installed wiring over electrical terminals.
Use NEC Class 1 wiring for all hazardous voltage electrical power supplies.
Check and retighten all wiring connections before starting the unit.
16-5/8"
(422mm)
7-1/4" (184mm)
33"
(838mm)
3-3/8"
(86mm)
3-1/4"
(83mm)
6-1/2"
(165mm)
36" (914mm)
Each piping outlet connection - A, B, C and D - is 2-5/8".
Secondary In
BCW OUT
BCW IN
Secondary Out
Floor Piping
A
C
B
D
Rear
Front
DPN002400
Pg. 3, Rev. 1
2-1/2"
(64mm)