Instruction manual
Micro Motion
®
 Model D and DT Sensors Instruction Manual 39
Installation
Step 5 Startup
Zeroing
After the flowmeter has been fully installed, you must perform the 
zeroing procedure. Flowmeter zeroing establishes flowmeter response 
to zero flow and sets a baseline for flow measurement. Refer to the 
transmitter instruction manual for information on performing the zeroing 
procedure.
Configuration, calibration, and 
characterization
You can use the transmitter to configure, calibrate, and characterize the 
meter. For more information, refer to the transmitter instruction manuals.
The following information explains the difference between configuration, 
calibration, and characterization. Certain parameters might require 
configuration even when calibration is not necessary.
Configuration parameters include such items as flowmeter tag, 
measurement units, flow direction, damping values, and slug flow 
parameters. If requested at time of order, the meter is configured at the 
factory according to customer specifications.
Calibration accounts for the flowmeter’s sensitivity to flow, density, and 
temperature. Calibration is done at the factory.
Characterization is the process of entering calibration factors for flow, 
density, and temperature directly into transmitter memory, instead of 
performing field calibration procedures. Calibration factors can be found 
on the sensor serial number tag and on the certificate that is shipped 
with the sensor.
For instructions about flowmeter configuration, calibration, and 
characterization, see the manual that was shipped with the transmitter.
If the sensor and transmitter are ordered together as a Coriolis 
flowmeter, the factory has characterized the meter — no additional 
characterization is necessary. If either the sensor or transmitter is 
replaced, characterization is required.