Troubleshooting guide

75
Reference Manual
00809-0100-4308, Rev BA
Section 6: Service and Troubleshooting
December 2014
Service and Troubleshooting
Table 6-2. Configuration Error Details (D:)
Message Description Recommended actions
Lower Range Value or Upper
Range Value is out of limits
The lower/upper range value is outside
the lower/upper sensor limits. This is
outside the range where the sensor
works properly, hence the measurement
may be unreliable.
1. Check the lower and upper range values in
relation to the sensor limits.
Configured Measurement
Mode not Supported
The configured Measurement Mode
does not work since support has not
been purchased.
1. Upgrade the device.
2. Change the Measurement Mode to match,
refer to “Measurement Mode” on page 162.
Volume Configuration Error The volume cannot be calculated
correctly with the current configuration.
1. Check that the level-volume values in the
strapping table are entered in increasing
order, refer to “Strapping Table” on
page 172.
2. Check that the number of strapping points
to use is correct.
3. Check size measures in the Volume Setup.
Parameter Out of Limits One or more of the configuration values,
in a set that belongs together, has been
changed and reduced the measurement
range of the device.
1. Check the configured values for Probe
Length, Vapor Dielectric Constant, and
Upper Product Dielectric Constant.
2. Restore default settings and reconfigure the
device.
Low Low Level Alert
configuration is invalid
Low Low Level Alerts will not be raised as
expected because of invalid
configuration.
1. Check entered limit and deadband values in
comparison with entered tank and probe
parameters such as probe length, tank
height etc.
Low Level Alert configuration
is invalid
Low Level Alerts will not be raised as
expected because of invalid
configuration.
1. Check entered limit and deadband values in
comparison with entered tank and probe
parameters such as probe length, tank
height etc.
High Level Alert configuration
is invalid
High Level Alerts will not be raised as
expected because of invalid
configuration.
1. Check entered limit and deadband values in
comparison with entered tank and probe
parameters such as probe length, tank
height etc.
High High Level Alert
configuration is invalid
High High Level Alerts will not be raised
as expected because of invalid
configuration.
1. Check entered limit and deadband values in
comparison with entered tank and probe
parameters such as probe length, tank
height etc.
User Defined Alert
configuration is invalid
User Defined Alerts will not be raised as
expected because of invalid
configuration.
1. Check entered limit and deadband values in
relation to the selected variable.
Signal Quality Alert
configuration is invalid
Signal Quality Alerts will not be raised as
expected because of invalid
configuration.
1. Check entered limit and deadband values
regarding their range [0.1 – 10.0] and
mutual relationship.
No user configuration errors
detected
No user configuration errors detected.