Troubleshooting guide
35
Reference Manual
00809-0100-4308, Rev BA
Section 3: Installation
December 2014
Installation
3.6.3 Tank connection with loose flange (“plate design”)
Figure 3-15. Tank Connection with Loose Flange
The transmitter is delivered with head, flange and probe assembled into one unit. If, for some
reason, these parts have been disassembled mount the transmitter as described below:
1. Place a gasket on top of the tank flange.
2. Mount the flange on the probe and tighten the flange nut.
3. Mount the transmitter head.
4. Lower the transmitter and probe with flange into the tank.
5. Tighten the bolts.
6. Loosen the nut that connects the transmitter head to the probe slightly.
7. Rotate the transmitter head so the device display faces the desired direction.
8. Tighten the nut. Max torque is 30 Lbft (40 Nm).
9. Continue with the grounding step.
A. Transmitter head
B. Nut
C. Flange nut
D. Bolts
E. Probe
F. Loose flange
G.Plate
H.Gasket
I. Tank flange
F
AA
B
C
D
E
G
H
I