Troubleshooting guide
34
Reference Manual
00809-0100-4308, Rev BA
Section 3: Installation
December 2014
Installation
3. Lower the transmitter and probe into the tank.
4. Loosen the nut that connects the transmitter head to the probe slightly.
5. Screw the adapter into the process connection.
6. Rotate the transmitter head so the device display faces the desired direction.
7. Tighten the nut. Max torque is 30 Lbft (40 Nm).
8. Continue with the grounding step.
3.6.2 Tank connection with flange
Figure 3-14. Tank Connection with Flange
1. Place a gasket on top of the tank flange.
2. Lower the transmitter and probe with flange into the tank.
3. Tighten the bolts.
4. Loosen the nut that connects the transmitter head to the probe slightly.
5. Rotate the transmitter head so the device display faces the desired direction.
6. Tighten the nut. Max torque is 30 Lbft (40 Nm).
7. Continue with the grounding step.
A
A. Transmitter head
B. Nut
C. Bolts
D. Flange
E. Probe
F. G as k et
G.Tank flange
B
C
E
D
F
G