Troubleshooting guide
33
Reference Manual
00809-0100-4308, Rev BA
Section 3: Installation
December 2014
Installation
3.6 Mount device on tank
Mount the transmitter with flange on a nozzle on top of the tank. The transmitter can also be
mounted on a threaded connection. Make sure only qualified personnel perform the
installation.
Note
If the transmitter head must be removed from the probe, make sure that the Process seal is
carefully protected from dust and water. See “Transmitter head replacement” on page 99 for
further information.
Note
PTFE covered probes must be handled carefully to prevent damage to the coating.
3.6.1 Threaded tank connection
Figure 3-13. Threaded Tank Connection
1. For adapters with BSP/G threads, place a gasket on top of the tank flange.
2. For adapters with NPT threads, use anti-seize paste or PTFE tape according to your site
procedures.
A. Transmitter head
B. Nut
C. Adapter
D. Probe
E. Sealant on threads (NPT) or
Gasket (BSP/G)
F. Tank flange/Process connection
E
F
A
B
C
D