Appendix D: Configuration Parameters
December 2014
Configuration Parameters
Inner Diameter,
Pipe/Chamber/Nozzle
Select the inner diameter for the pipe, chamber or nozzle in
which the probe is mounted.
Nozzle Height The distance between the Upper Reference Point (normally
the lower side of the device flange) and the end of the nozzle.
Note that nozzle may extend into the tank (which should be
included in the height).
Measurement Mode Select the Measurement Mode to use in the device. Some
modes require software options to be enabled in the device.
You can upgrade the device to enable more software options.
Interface Level with Submerged Probe is used for applications
where the probe is fully immersed in liquid. In this mode the
transmitter ignores the upper product level. See “Interface
measurements with fully submerged probes” on page 96 for
more information.
Note
Only use Interface Level with Submerged Probe for
applications where interface is measured for a fully immersed
probe.
Upper Product Media Approximate DC value selected from list based on tank
content.