Troubleshooting guide
132
Reference Manual
00809-0100-4308, Rev BA
Appendix A: Reference Data
December 2014
Reference Data
Figure A-14. Rigid Single Lead Probe
Recommended: D > 4 (100)
Minimum: D=1.5 (38) for probe type 4A
(1)
D=2 (50) for probe type 4B
(1)
Dimensions are in inches (millimeters).
12 (297.2)
3.9 (100.2)2.8 (71.3)
External antenna
(option WK)
Ø 0.31 (8) or Ø 0.51 (13): SST probe
Ø 0.47 (12): PTFE covered probe
BSP-G 1 in., s52
BSP-G 1½ in., s60
2.4 (62)
Thread sealing
Min. 8 (200)
Chamber/pipe
Min. Ø 2 (50)
NPT 1 in., s52
NPT 1½ in., s52
NPT 2 in., s60
1.9 (47)
2.4 (62)
3.4 (86)
4.3 (110)
L 10 ft (3 m)
for Ø 0.31 (8)
L 20 ft (6 m)
for Ø 0.51 (13)
PTFE covered probe
and protective plate
Protective
plate
Min. 0.2 (5)
The probe must be
in the center of the
probe/chamber
Ø D (Nozzle diameter)
Min. 4 (100) if smooth metallic wall.
Min. 16 (400) if disturbing objects or
rugged metallic wall.
7.8 (198)
Nozzle height (H)
H < 4 (100) + D
Tri- Clamp
connection
12 (297.2)
(1) The Trim Near Zone (TNZ) function may be
necessary or an Upper Null Zone (UNZ)
setup may be required to mask the nozzle.