Troubleshooting guide
100
Reference Manual
00809-0100-4308, Rev BA
Section 6: Service and Troubleshooting
December 2014
Service and Troubleshooting
6.8 Probe replacement
Figure 6-19. Probe Replacement
1. Loosen the nut.
2. Remove the transmitter head from the old probe. Make sure to protect the transmitter
head bottom from dust and water.
3. On the new probe, make sure that the protection plug is removed and the upper
surface of the Process Seal is clean. Also make sure that the spring-loaded pin at the
center of the Process Seal is properly inserted.
4. Mount the transmitter head on the new probe.
5. Tighten the nut. Max torque is 30 Lbft (40 Nm).
6. If the new probe is not of the same type as the old one, update the transmitter
configuration by setting the Probe Type parameter to the appropriate value:
a. From the Home Screen, go to Configure > Manual Setup > Level Setup > Probe.
b. Under Probe Type, select desired Probe Type.
7. Measure the Probe Length and enter the measured value:
a. From the Home Screen, go to Configure > Manual Setup > Level Setup > Probe.
b. Under Probe Length, enter the measured Probe Length value.
8. Run Verify Level to check your level measurement, refer to “Verify Level” on page 59.
Threaded version
B
Flange version
C
A. Transmitter head
B. Nut
C. Process Seal
D. Probe
A
B
D
C
A
B
D