Datasheet

UPS Specifications — 5, 6 and 10kVA models
6
Power Distribution Specifications
Model Number GXT3-5000RT230 GXT3-6000RT230 GXT3-10000RT230
Rating (VA / W) 5000VA / 4000W 6000VA / 4800W 10000VA / 9000W
Physical Dimensions
Unit: W x D x H (mm) / (in) 430 x 574 x 217 / 16.9 x 22.4 x 8.5 430 x 581 x 261 / 16.9 x 22.9 x 10.3
Shipping: W x D x H (mm) / (in) 530 x 745 x 516 / 20.9 x 29.3 x 20.3 530 x 745 x 563 / 20.9 x 29.3 x 22.2
Weight
Unit (kg) / (lb) 60 / 132.2 70 / 154.3
Shipping (kg) / (in) 71 / 156.5 92 / 202.8
Input AC Parameters
Operating Frequency 50 or 60Hz Nominal (factory default = 50)
Factory Default 230VAC
User-Configurable 220 / 230 / 240VAC
Operating Voltage Range (without battery operation) 176 to 280VAC
Maximum Allowable 280VAC
Input Frequency (without battery operation) 40 to 70Hz
Input Power Connection PD2-CE6HDWRMBS Standard PD2-CE10HDWRMBS Standard
Output AC Parameters
Factory Default 230VAC
Output Connections PD2-CE6HDWRMBS Standard PD2-CE10HDWRMBS Standard
Frequency 50Hz or 60Hz Nominal
Waveform Sinewave
Main Mode Overload > 200% for 5 cycles; 151 to 200% for 1 seconds; 131to 150% 10 seconds; 105 to 130% 1 minute
Battery Parameters
Typ e Valve-regulated, non-spillable, lead acid
Quantity 20 x 12V
Recharge Time (internal batteries) 3 hrs to 90% capacity after full discharge into 100% load
Bypass Protection Limits
Disable Bypass Operation If input voltage exceeds ±15% of the nominal voltage
Re-Enable Bypass Operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass Operation When the input frequency prevents synchronous operation
Environmental
Operating Temperature (°C) (°F) 0 to 40 (32 to 104)
Storage Temperature -15 to 50 (5 to 122)
Relative Humidity 0 to 95%; non-condensing
Operating Elevation Up to 1000m (3281 ft) at 30°C (86°F) without derating
Audible Noise < 55 dBA at 1 meter from the rear; < 50 dBA at 1 meter from the front or sides
Agency Approvals
Safety IEC62040-1:2008 version
EMI / EMC IEC / EN / AS 62040-2 2nd Ed (Cat 2 – Table 6)
ESD EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient EN61000-4-4, Level 4, Criteria A
Surge Immunity EN61000-4-5, Level 3, Criteria A
Transportation ISTA Procedure 1A
Model Number PD2-CE6HDWRMBS PD2-CE10HDWRMBS
Amp Rating (Amps) 32 63
Input Power Connection 3-Wire Hard-Wired; 6-10mm2 (8-10AWG)
Output Power Connection 3-Wire Hard-Wired, 6-10mm2 (8-10AWG)
Includes Two IEC320 C19 16A/250V Sockets
Six C13 10A/250V Sockets
Manual Bypass Switch with Indicator Lamps
Four IEC320 C19 16A/250V Sockets,
Four C13 10A/250V Sockets
Manual Bypass Switch with Indicator Lamps
Input Branch Circuit Breaker, Supplied by User 32A 63A
Product Specifications