User manual
Specifications
32
Table 11 Environmental data
Environmental Parameter
Value
Operating Temperature, °C (°F) 0 to 40 (32 to 104) refer to Table 13 - Operating temperature parameters
Storage Temperature, °C (°F) 15 to 50 (5 to 122)
Relative Humidity 0-95% non-condensing
Operating Elevation Up to 1000m (3281 ft) at 30°C (86°F) without derating
Audible Noise
<55 dBA, at 1 meter (39") from the rear; <50 dBA, at 1 meter (39") from the
front or sides
Table 12 Agency/safetycompliance
EMI/EMC/C-Tick EMC IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6)
ESD EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient EN61000-4-4, Level 4, Criteria A
Surge Immunity EN61000-4-5, Level 3, Criteria A
Transportation ISTA Procedure 1A
Table 13 Operating temperature parameters
Ambient Temperature, °C (°F)
pf @30°C ±3°C
(pf @ 86°F ±5.4°F)
pf @40°C ±3°C
(pf @ 104°F ±5.4°F)
10000T230 0.9pf 0.8pf
Table 14 Typical battery run times, minutes at 25°C (77°F), 100% resistive load
Number of Batteries,
Battery Cabinets
Load %
30% 40% 50% 60% 70% 80% 90% 100%
Internal Battery 21 14.5 10.75 8.5 6.5 5 3.75 3
Internal Battery
+ 1 External Battery Cabinet
43 33 26 21 17 13 11.5 10
Internal Battery
+ 2 External Battery Cabinets
74.5 55 41.5 33 28.5 24 21 18
Internal Battery
+ 3 External Battery Cabinets
95 70 58 48 40 34 29.5 26
Internal Battery
+ 4 External Battery Cabinets
99.5 96 72.5 62 51 45 40 34