Datasheet
Energia CA
Para Business-Critical Continuity
™
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™.
Emerson Network Power
Liebert Corporation World Headquarters
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43229
United States Of America
800 877 9222 Phone (U.S. & Canada Only)
614 888 0246 Phone (Outside U.S.)
614 841 6022 FAX
Contact@EmersonNetworkPower.com
Emerson Network Power
Caribbean and Latin America
Ofce – United States of America
+1-954-984-3452 Phone
Ask.Cala@Emerson.com
liebert.com
24 x 7 Tech Support
800 222 5877 Phone
614 841 6755 (outside U.S.)
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™.
AC Power
Embedded Computing
Outside Plant
Racks & Integrated Cabinets
Connectivity
Embedded Power
Power Switching & Controls
Services
DC Power
Infrastructure Management
& Monitoring
Precision Cooling
Industrial Power
Business-Critical Continuity, Emerson Network Power and the
Emerson Network Power logo are trademarks and service marks of
Emerson Electric Co.
©2013 Emerson Electric Co.
While every precaution has been taken to ensure accuracy and
completeness in this literature, Liebert Corporation assumes no
responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions.
© 2013 Liebert Corporation. All rights reserved throughout
the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks
of their respective owners.
® Liebert is a registered trademark of the Liebert Corporation.
SL-23182 (R03/13) Printed in USA
Specifications
Model Number GXT3-500RT120 GXT3-700RT120 GXT3-1000RT120 GXT3-1000MT120
TAA Compliant
Part Number
N/A N/A GVG3-1000RT120 N/A
Model Rating VA/W 500/450 700/630 1000/900 1000/900
Dimensions: in. (mm)
DxWxH
19.7 x 16.9 x 3.4
(497 x 430 x 85)
15.4 x 6.9 x 8.9
(390 x 175 x 225)
Weight: lbs. (kg) 44 (20)
Input AC Parameter
Voltage Range 120VAC nominal; variable based on output load
Frequency 40Hz
~
70Hz; Auto Sensing
Input Power Cord 10 ft. attached w/ NEMA 5-15P plug
Output AC Parameter
Output Receptacles 5-15R x 6
Voltage 110/115/120/127VAC (user-configurable); ±3%
Waveform Sine wave
Battery
Full Load 17 minutes 11 minutes 7 minutes 7 minutes
Half Load 34 minutes 27 minutes 17 minutes 17 minutes
Recharge Time 6 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown
Agency
Safety UL 1778, cUL Listed
RFI/EMI FCC Part 15, Class A=CISPR22 Class B
Surge Immunity IEC 62040-2 2nd Ed
Transportation ISTA Procedure 1A
ENERGY STAR
®
qualifed No Yes Yes No
Model Number GXT3-1500RT120 GXT3-2000RT120 GXT3-3000RT120 GXT3-3000RT208
TAA Compliant
Part Number
GVG3-1500RT120 GVG3-2000RT120 GVG3-3000RT120 N/A
Model Rating VA/W 1500/1350 2000/1800 3000/2700 3000/2700
Dimensions: in. (mm)
DxWxH
19.7 x 16.9 x 3.4
(497 x 430 x 85)
23.7 x 16.9 x 3.4
(602 x 430 x 85)
Weight: lbs. (kg) 48.5 (22) 52.9 (24) 61.7 (28) 61.7 (28)
Input AC Parameter
Voltage Range 120VAC nominal; variable based on output load
208VAC nominal;
variable based on
output load
Frequency 40Hz
~
70Hz; Auto Sensing
Input Power Cord
10 ft. attached w/
NEMA 5-15P plug
10 ft. attached w/
NEMA 5-20P plug
10 ft. attached w/
NEMA L5-30P plug
10 ft. attached w/
NEMA L6-20P plug
Output AC Parameter
Output Receptacles 5-15R x 6 5-20R x 6 L5-30R x 1+5-20R x 6 L6-20R x 1+L6-15R x 2
Voltage
110/115/120/127VAC
(user-configurable); ±3%
208/220/230/240 VAC
(user-configurable); ±3%
Waveform Sine wave
Battery
Full Load 4 minutes 3 minutes 3 minutes 3 minutes
Half Load 11 minutes 11 minutes 11 minutes 11 minutes
Recharge Time 6 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown
Agency
Safety UL 1778, cUL Listed
RFI/EMI FCC Part 15, Class A=CISPR22 Class B
Surge Immunity IEC 62040-2 2nd Ed
Transportation ISTA Procedure 1A
ENERGY STAR
®
qualifed Yes Yes Yes Yes