User manual
Liebert GXTRT Series Installation and User Manual
1-3 kVA UPS
Page 25 9/2005 Emerson Network Power
S
p
ecifications
Chapter 5 Specifications
5.1 Mechanical
Module W×H×D (mm) Weight (kg)
Power module GXT1000-RT 440×87×400 17.5
Power module GXT1000L-RT 440×87×400 7.8
Power module GXT2000-RT 440×87×400 8.6
Power module GXT2000L-RT 440×87×400 9.6
Power module GXT3000-RT 440×87×400 9.0
Power module GXT3000L-RT 440×87×400 10.0
Battery module GXT2000-BAT 440×87×400 20.5
Battery module GXT3000-BAT 440×87×400 21.5
5.2 Electrical
Model
GXT
1000-RT
GXT
1000L-RT
GXT
2000-RT
GXT
2000L-RT
GXT
3000-RT
GXT
3000L-RT
Rating 1000VA/700W 2000VA/1400W 3000VA/2100W
Input system 1-phase, plus PE
Rated voltage 220Vac / 230 Vac / 240 Vac
Voltage range
1. 176~288Vac, full load
2. <176Vac, linear derating
3. 120Vac, half load
Frequency 50Hz±10%
Input
Power factor
0.99 (conditions: rated voltage, full pure resistive load, fully
charged battery)
Output system 1-phase, plus PE
Power factor 0.7
Voltage 220 Vac / 230 Vac / 240 Vac +/-2%
Line regulation ≤2%(0~100% linear load)
Output
Load regulation ≤2%(0~100% linear load)
Voltage harmonic
distortion (rated
input voltage,
rated input
frequency)
≤2%(0 ~100% linear load)
≤5%(0 ~100% non-linear load)
Dynamic transient
response
IEC62040-3 Class 1
Dynamic response
recovery
IEC62040-3 (60ms) Class 1
Frequency
The output frequency synchronizes with the bypass frequency
when the bypass frequency is in the range of 50Hz±10%, with the
phase difference less than 3 degrees; the output frequency is
50Hz when the bypass frequency is outside specifications or the
bypass voltage is lower than 120Vac
Output
Frequency
synchronization
speed
1 Hz/s