User manual

Liebert GXTRT Series Installation and User Manual
1-3 kVA UPS
Page 19 9/2005 Emerson Network Power
O
p
eration
Table 3-1 LED indication
BATTERY indicator (green)
It illuminates when the UPS is on battery and the
battery voltage is not too high, flashes when the
battery is faulty or the charging voltage is too high
INVERTER indicator (green)
It illuminates when the inverter is in normal operation,
flashes when the inverter is faulty
BYPASS indicator (green) It illuminates when the UPS is on bypass.
LINE indicator (green)
It illuminates when the mains input is normal, flashes
when abnormal, and goes off when it fails
ALARM indicator (red) It is on in the event of a UPS fault, off otherwise.
The buzzer and the ten indicators combine to indicate the UPS operating status and faults, as
illustrated in Table 3-2:
Table 3-2 Audible alarm and LED indication of UPS operating status and fault
s
LED number (identified in Figure 3-1) S/
N
Operating status
1 2 3 4 5 6 7 8 9 10
Audible alarm
1 0%~25% load
None
2 26%~50% load
None
3 51%~75% load
None
4 76%~100% load
None
5 101%~105% load
None
6
Normal
mode
>105% load
Twice every 1s
7
0%~25% battery
capacity
Once every 1s
8
26%~50% battery
capacity
Once every 3.3s
9
51%~75% battery
capacity
Once every 3.3s
10
76%~95% battery
capacity
Once every 3.3s
11
>96% battery
capacity
Once every 3.3s
12
Battery
mode
>105% load
Twice every 1s
13 Shortcircuit fault
Continuous
14 Charger fault
Continuous
15 Overheating fault
Continuous
16 Fan failure
Once every 1s
17 Rectifier fault
Continuous
18 Inverter fault
¤
Continuous
19 Inverter overload
Continuous
20
Battery overcharge
(in Normal mode)
¤
None
21
Battery overcharge (in Standby
state)
¤
None
22 No battery
¤
6 times
ON; depending on other conditions; ¤ Flash
Note
LED 1 is yellow, LED 6 is red, others are green.