User manual

Liebert GXTRT Series Installation and User Manual
1-3 kVA UPS
Page 14 9/2005 Emerson Network Power
Installation
2. Use step 2 in section 2.3.1 to put the power module and battery module on the bases, with
the power module in the right position to facilitate cable connection, as shown in Figure 2-4.
Figure 2-4 Positioning modules
2.4 Rack Installation
2.4.1 Installing Single Power Module
Use the following steps to install the UPS systems that contain only one power module and no
battery module. These power modules include GXT1000-RT, GXT1000L-RT, GXT2000L-RT
and GXT3000L-RT.
1. Take out the pair of brackets delivered with the power module; remove the four flat screws
M4*8 on both sides of the module, as shown in Figure 2-5; and fix the brackets onto both sides
of the module using the flat screws, as shown in Figure 2-6.
Figure 2-5 Removing flat screws
Figure 2-6 Installing brackets
2. Place the power module onto the slide rail in the rack in the direction shown in the following
figure, and push it into place along the slide rail. Fix the module onto the rack using four screws
(provided by the user), as shown in the figure below.
Figure 2-7 Installing power module