Safety
Information
Product information
Mechanical
installation
Electrical
installation
Getting started Running the motor
SMARTCARD
operation
Advanced
parameters
Diagnostics UL listing
1.4 Environmental limits
Instructions within the supplied data and information within the Mentor MP User Guide
regarding transport, storage, installation and the use of the drive must be complied with,
including the specified environmental limits. Drives must not be subjected to excessive
physical force.
1.5 Access
Access must be restricted to authorized personnel only. Safety regulations which apply
at the place of use must be complied with.
1.6 Fire protection
The drive enclosure is not classified as a fire enclosure. A separate fire enclosure must
be provided.
1.7 Compliance with regulations
The installer is responsible for complying with all relevant regulations, such as national
wiring regulations, accident prevention regulations and electromagnetic compatibility
(EMC) regulations. Particular attention must be given to the cross-sectional areas of
conductors, the selection of fuses and other protection, and protective ground (earth)
connections.
The Mentor MP User Guide contains instructions for achieving compliance with specific
EMC standards.
Within the European Union, all machinery in which this product is used must comply
with the following directives:
2006/42/EC: Safety of machinery
2004/108/EC: Electromagnetic compatibility
1.8 Motor
Ensure the motor is installed in accordance with the manufacturer's recommendations.
Ensure the motor shaft is not exposed.
Low speeds may cause the motor to overheat because the cooling fan becomes less
effective. The motor should be installed with a protection thermistor. If necessary, an
electric forced ventilation fan should be used.
The values of the motor parameters set in the drive affect the protection of the motor.
The default values in the drive should not be relied upon.
It is essential that the correct value is entered into Pr 5.07 (SE07, 0.28), Motor rated
current. This affects the thermal protection of the motor.
1.9 Adjusting parameters
Some parameters have a profound effect on the operation of the drive. They must not
be altered without careful consideration of the impact on the controlled system.
Measures must be taken to prevent unwanted changes due to error or tampering.