Table 4-14 Ferraz Shawmut semiconductor fusing for USA size 2 drives
Model
USA
Description Catalogue number Ref number
Field fuses 10 x 38mm Ferrule FR10GB69V25 L330014
MP350A4
American
Round Fuses
Form 101
Range A70QS
A50QS450-4 A7OQS450-4
EQ16871
F214848
MP350A4R A7OQS450-4 F214848
MP350A5
MP350A6
A70QS450 F214848
MP350A5R
MP350A6R
MP420A4 A50QS600-4 A70QS600-4
Q219457
Y219993
MP420A4R A70QS600-4 Y219993
MP470A5
MP470A6
2 x A70QS400 in parallel J214345 (x2)
MP470A5R
MP470A6R
MP550A4 A50QS700-4 A70QS700-4
N223181
E202772
MP550A4R A70QS700-4 E202772
MP700A4
A50QS900-4
2 x A70QS500-4 in parallel
R212282
A218431 (x2)
MP700A4R
2 x A70QS500 in parallel A218431 (x2)
MP700A5
MP700A6
MP700A5R
MP700A6R
MP825A4
A50QS1200-4
2 x A70QS600-4 in parallel
C217904
Y219993 (x2)
MP825A5
MP825A6
2 x A7OQS600-4 in parallel Y219993 (x2)
MP825A4R
MP825A5R
MP825A6R
MP900A4
A50QS1200-4
2 x A7OQS600-4 in parallel
C217904
Y219993 (x2)
MP900A4R 2 x A7OQS600-4 in parallel Y219993 (x2)
MP1200A4
2 x A5OQS800-4 in parallel
2 x A70QS800-4 in parallel
C202287 (x2)
Z213830 (x2)
MP1200A4R
2 x A70QS800-4
in parallel
Z213830 (x2)
MP1200A5
MP1200A6
MP1200A5R
MP1200A6R
MP1850A4
2 x A5OQS1000-4 in parallel
*3 x A7OQS700-4 in parallel
B217391 (x2)
*E202772 (x3)
MP1850A4R
*3 x A7OQS700-4
in parallel
*E202772 (x3)
MP1850A5
MP1850A6
MP1850A5R
MP1850A6R
A50QS series are only rated up to 500Vac.
*Application overload limited to infrequent overloads to avoid fuse wear out
**Fuse limits applications to those operating at rated current. No cyclic overloads permitted.
NOTE