Data Sheet

A11 Valve
D500203X012
Product Bulletin
21.1:A11
May 2013
18
Table 19. Maximum Allowable Shutoff Pressure Drops, CL600
(1)
TRIM
NUMBER
TEMP RANGE NPS 3 NPS 4 NPS 6 NPS 8 NPS 10 NPS 12 NPS 14 NPS 16 NPS 18 NPS 20 NPS 24
_C Bar
500
-46 to 38 98.9 103.1 103.4 103.4 99.1 103.4 1 03.4 103.4 103.4 103.4 60.9
38 to 93 75.8 75.8 75.8 75. 8 75.8 75.8 75.8 75.8 75.8 75.8 60.9
93 to 121 41.4 41.4 41.4 41.4 41.4 41.4 41.4 41.4 41.4 41.4 41.4
121 to 149 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9
502
-46 to 38 95.0 100.4 103.4 103.4 98.0 92.2 103.4 103.4 103.4 94.8 55.2
38 to 232 82.3 87.6 82.1 95.1 86.9 74.1 103.4 103.4 10 3.4 94.8 55.2
504
-46 to 38 93.1 100.1 103.4 103.4 98.1 87.1 103.4 103.4 103.4 84.7 46.2
38 to 93 79.5 94.3 96.5 96. 5 93.0 79.2 96.5 96.5 96.5 84.7 46.2
93 to 121 62.1 62.1 62.1 62.1 62.1 62.1 62.1 62.1 62.1 62.1 46.2
121 to 149 20.7 20.7 20.7 20.7 20.7 20.7 20.7 20.7 20.7 20.7 20. 7
506
-46 to 38 91.8 98.4 75.4 103.4 95.6 65.7 103.4 103.4 93.3 67.2 38.1
38 to 343 62.1 78.9 51.4 76.5 82.2 48.4 101.8 83.2 93.3 67.2 38.1
343 to 427 58.7 75.1 48.8 73.3 80.5 46.5 98.5 80.5 93.3 67.2 38. 1
514H,
516H
343 to 427 58.7 75.1 48.8 73.3 80.5 46.5 98.5 80.5 93.3 67.2 38. 1
514H
(2)
,
516H
427 to 538 97.8 103.4 83.6 103.4 101.2 71.7 103.4 103.4 93.4 67 .2 38.1
517C -196 to 163 Consult your Emerson Process Management sales office.
517C
(3)
-196 to -129 88.4 92.3 100.2 98.7 89.9 103.4 103.4 103.4 103.4 103.4 78.3
-129 to -46 79.6 83.2 90.3 89.1 81.6 94.8 102.3 103.4 10 3.4 103.4 78.3
-46 to 38 67.6 70.7 76.7 76. 3 70.3 77.6 88.6 93.1 94.5 103.4 78.3
38 to 149 61.2 64.1 69.5 69.4 64.3 66.7 81.2 85.1 86.3 96.5 78.3
TRIM
NUMBER
_F Psi
500
-50 to 100 1435 1495 150 0 1500 1437 1500 1500 1500 1500 1500 883
100 to 200 1100 1100 1100 1100 1100 1100 1100 1 100 1100 1100 883
200 to 250 600 600 600 600 600 600 600 600 600 600 600
250 to 300 100 100 100 100 100 100 100 100 100 100 100
502
-50 to 100 1378 1456 150 0 1500 1422 1337 1500 1500 1500 1375 800
100 to 450 1194 1270 1191 1380 1260 1075 1500 1 500 1500 1375 800
504
-50 to 100 1350 1453 150 0 1500 1422 1264 1500 1500 1500 1229 670
100 to 200 1153 1368 1400 1400 1349 1148 1400 1 400 1400 1229 670
200 to 250 900 900 900 900 900 900 900 900 900 900 670
250 to 300 300 300 300 300 300 300 300 300 300 300 300
506
-50 to 100 1331 1427 109 3 1500 1401 953 1500 1500 1353 974 553
100 to 650 900 1144 746 111 0 1192 702 1477 1206 1353 974 553
650 to 800 852 1089 708 106 4 1167 675 1429 1168 1353 974 553
514H,
516H
650 to 800 852 1089 708 106 4 1167 675 1429 1168 1353 974 553
514H
(2)
,
516H
800 to 1000 1418 1500 1213 1500 1468 1040 1500 1500 1354 974 553
517C -320 to 325 Consult your Emerson Process Management sales office.
517C
(3)
-320 to -200 1282 1339 1454 1431 1304 1500 1500 1500 1500 1500 1135
-200 to -50 1155 1206 1309 1293 1184 1375 1484 1500 1500 1500 1135
-50 to 100 980 1025 1113 1106 1020 1126 1285 1350 1371 1500 1135
100 to 300 887 929 1008 1006 933 967 1178 1234 1251 1400 1135
1. Consult your Emerson Process Management sales office if higher pressure drops are required.
2. Trim 514H with optional N07718 shaft for temperatures up to 482_C (1000_F).
3. Trim 517C with optional CTFE cryogenic seal without backup ring.