Data Sheet

Level Instruments
D103219X012
Product Bulletin
11.2:Level
February 2015
14
Table 13. Fisher 2500 Controller/Transmitter Supply Pressure
Output Signal
Standard Supply and
Output Pressure Gauge
Indications
(1)
Normal Operating
Supply Pressure
(2)
Air Consumption at Normal Operating
Supply Pressure
(3)
Normal m
3
/h
(4)
Scfh
(4)
Bar Psig Min
(5)
Max
(6)
Min
(5)
Max
(6)
0.2 to 1.0 bar (3 to 15 psig),
except 0 and 1.4 bar (0 and 20
psig)
(2)
for on‐off controllers
0 to 30 psig 1.4 20 0.11 0.72 4.2 27
0.4 to 2.0 bar (6 to 30 psig),
except 0 and 2.4 bar (0 and 35
psig)
(2)
for on‐off controllers
0 to 60 psig 2.4 35 0.19 1.1 7 42
1. Consult your Emerson Process Management sales office about gauges in other units.
2. Control and stability may be impaired if this pressure is exceeded (except 2503 or 2503R controller without proportional valve).
3. Except 2503 or 2503R controller, which bleeds only when relay is open at exhaust position.
4. Normal m
3
/hr=normal cubic meters per hour at 0_C and 1.01325 bar. Scfh=standard cubic foot per hour at 60_F and 14.7 psia.
5. At zero or maximum proportional band or span setting.
6. At setting in middle of proportional band or span range.
Figure 13. Typical Controller
W0656‐1