Instruction Manual

Instruction Manual
D103531X012
L2e Controller
June 2014
4
Table 1. Specifications (continued)
Hazardous Area Classifications Available
Switch Only
cCSAus
Explosion-proof Class I Division 1, Groups ABCD
Dust Ignition-proof Class II Division 1, Groups EFG
Dual Seal
ATEX II 2 GD
Flameproof Ex d IIC T6 (Ta=40°C to + 75°C)
Dust Ex tb IIIC T85°C Db IP6X (Ta = 40° to +75°C)
1 A Max
IECEx
Flameproof Ex d IIC T6 (Ta=40°C to + 75°C)
Dust Ex tb IIIC T85°C Db IP6X (Ta = 40° to +75°C)
1 A Max
Canadian Registration (CRN)
The L2e utilizes the same sensor unit pressure
component as the L2 pneumatic controller version.
Refer to the L2 CRN which is deemed applicable to
the L2e.
Declaration of SEP
Fisher Controls International LLC declares this
product to be in compliance with Article 3 paragraph
3 of the Pressure Equipment Directive (PED) 97 / 23 /
EC. It was designed and manufactured in accordance
with Sound Engineering Practice (SEP) and cannot
bear the CE marking related to PED compliance.
However, the product may bear the CE marking to
indicate compliance with other applicable European
Community Directives.
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1  Process Instrument Terminology.
1. Converting from a threaded NPT connection to a flange connection is to be done by the end-user. Refer to Converting a Threaded NPT Connection to a Flange Connection instruction Manual
Supplement (D103277X012), available at www.Fisher.com or from your Emerson Process Management sales office.
2. Maximum span setting with 1 7/8 x 12 inch horizontal displacer plus 6 inch extension is not recommended due to potentially insufficient zero adjustment.
3. The pressure and temperature limits in this document and any applicable code limitations should not be exceeded.
Installation
WARNING
Always wear protective clothing, gloves, and eyewear when performing any installation operations to avoid personal
injury.
To avoid personal injury or property damage caused by the sudden release of process fluid, be certain the service
conditions do not exceed the sensor pressure limits. Use pressurelimiting or pressurerelieving devices to prevent service
conditions from exceeding these limits.
Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
If installing this into an existing application, also refer to the WARNING at the beginning of the Maintenance section of this
instruction manual.
CAUTION
If the L2e electric level controller is installed on a vessel that is to be shipped to a different location (e.g. skid mounted
units), remove the displacer and displacer rod extensions before shipment. Failure to do so could result in damage to the
instrument and or the displacer rod due to vibration and impact loading during shipment. After the vessel is installed at its
final location, reassemble the displacer and displacer rod extension.
Note
Use with easyDrive electric actuator after first being used in other high power application is not recommended.